Data Center Solutions

AI load is an entirely new burden for the power grid

GPU clusters swing their power draw in milliseconds – not smoothly, the way traditional data centers do. An AI training cluster can swing 30-50% above base load in under one second, and those fast swings propagate out into the grid and toward local generation.

Two problems decide whether the project succeeds

A viable connection to solve both at once – and the same equipment has to do it.

  • Fast power swings degrade power quality at the connection point.
  • Torsional pulsation wears generators and motors over time.
  • The grid company can reject a load that is too variable.
  • On a grid fault the data center must not suddenly disconnect.
  • A sudden dropout threatens grid stability.
  • The grid owner requires ride-through – staying connected through faults.

The solution

A grid-forming BESS in parallel

A battery energy storage system running in parallel absorbes the swings and forms a stable interface to the grid.

  • Smooths the load toward the source – the grid, turbine or motor is proteced.
  • Rides through grid faults without destabilizing the nework.
  • The same solution works both grid-connected and in island mode.

Response time – Why milliseconds decide the outcome

Grid-following control is too slow – a two-to three-digit millisecond delay from the controller. Traditional grid-forming reacts within a frew mililseconds, but compensates only part of the swing. Fast Grid Forming compensates close to 100% of the load swing.

Traditional grid-forming figure: 40-60% depending on grid strength. Source: EPC Power

The battery is not kept full – it cycles for long life

  • Cyclic operation around ~50% state of charge – deliberately not permanently full.
  • High state of charge combined with heat accelerates ageing – which we avoid.
  • the energy management system keeps the charge level inside a target band.
  • Reserve for ride-through stays available without keeping the battery full.

UPS

The PSW utility‑scale outdoor UPS (Uninterruptible Power Supply) system offers a modern alternative to traditional data‑center UPS infrastructure. By integrating advanced energy‑management software, grid‑stabilization technologies, and our deep expertise in electrical power systems, the solution delivers true UPS‑grade power quality directly at the medium‑voltage level.

Installed outdoors and connected to the facility’s MV grid interface, the system ensures continuous, high‑quality power with or without diesel‑generator backup. This architecture significantly reduces system complexity and CAPEX while enabling bidirectional power flow, allowing excess energy to be exported back to the grid.

The solution combines:

One solution. Endless function.

Power disturbances mitigated by a UPS

UPS (Uninterruptible Power Supply) ensures continuous, stable power delivery to critical electrical equipment. Its primary function is to protect connected loads from power disturbances and to keep them operating during outages until the utility supply returns or backup generators take over. If no secondary power source is available, the UPS provides sufficient battery runtime to allow for a controlled shutdown, preventing data loss or equipment damage. Depending on the UPS rating and required autonomy, batteries may be installed internally or externally.

A UPS safeguards equipment against a wide range of grid-related or installation-related power quality issues:

Power outage (Blackout)

A complete loss of electrical power in part of or across the entire grid, affecting anything from a single building to a large geographical area.

Frequency variations

Typically caused by load fluctuations on the public grid, affecting equipment with electromagnetic components such as motors.

Sag & Brownout

A complete loss of electrical power in part of or across the entire grid, affecting anything from a single building to a large geographical area.

Harmonic distortion

Voltage or current waveform distortion, usually generated by nonlinear loads within building

Over-voltage

A complete loss of electrical power in part of or across the entire grid, affecting anything from a single building to a large geographical area.

Transients/surges

Short-duration voltage spikes caused by lightning strikes or switching operations within the electrical installation.

Operating modes of UPS systems

UPSs support several operating modes, including high-efficiency configurations

UPS MODE


The UPS continuously converts incoming AC power to DC via the rectifier and then back to AC through the inverter. The batteries are connected to the DC bus and remain charged. This mode provides full voltage and frequency regulation, delivering clean, stable power regardless of grid disturbances. It offers maximum protection but has higher energy consumption. The batteries are activated when the utility supply fails. The UPS switches to battery power with zero transfer time, ensuring uninterrupted, conditioned output to the load.

UPS & STATCOM MODE


In addition to UPS Mode, the power modules operate in STATCOM mode to ensure power factor correction and voltage quality regulation on both input and output.

BYPASS MODE


The bypass switch feeds the load directly from the bypass source. This occurs during internal UPS faults or short‑circuit conditions that exceed inverter capacity. It is also used when transferring the load to a maintenance bypass for service activities.

UPS ECO


A traditional high‑efficiency mode where the load is supplied through the bypass, with the UPS operating in parallel with the grid and the load.

UPS ECO STATCOM


A traditional high‑efficiency mode where the load is supplied through the bypass, with the UPS operating in parallel with the grid and the load. The power modules operate in STATCOM mode to ensure power factor correction and voltage quality regulation on both input and output.

UPS products

UPS
Up to Input/Output 2,5MVA 690VAC
4x1220A DC Connection
Battery Connection
UPS
Up to Input/Output 3,75MVA 690VAC
4x1170A DC Connection
Battery Connection

Battery products

Cabinets
1500VDC
379kWh 1CP Application
407-705kWh
0,5CP Application
Containers
1500VDC
3,75MWh 1CP Application
4,07MWh 0,5CP Application
5,6MWh 0,25CP Application
Stacked
1500VDC
8,4MWh 0,5CP Application

Four reasons to choose PSW


We master the technology

Load smoothing and ride-through, proven in practice


We handle the grid dialogue

Capacity, NVF 2025/2026, islanding and grid-connection contribution.


We secure the requirements

The equipment meets both end-customer`s and the grid owner` s requirements.


We reduce risk

One accountable partner / a shorter path to commissioning.

The building blocks we deliver

A complete, integrated package / from grid-forming inverters and batteries to power quality and control software.

Grid-forming inverters

0.6-7.5MW

>99% efficiency

Modular energy-storage inverters with Fast Grid Forming that provide load smoothing and ride-through in one device.

Battery energy storage (BESS)

Cabinets to 705kWh

Containers to 5.6MWh

1500 VDC cabinets, containers and stacked systems sized for the required autonomy and cycling profile.

Utility-scale UPS

Up to 3.75MVA

690VAC

Outdoor, medium-voltage UPS that delivers true UPS-grade power quality with or without generator backup, and can export excess energy back to the grid.

STATCOM

Up to 5MVA

690VAC

MV skid to 36kV

Fast, precise reactive-power support for voltage stability and power quality at the connection point.

DC switchboards

5-15MW

The central hub tying batteries, generation and fast-response loads together with modular protection.

Energy control & management software

Real-time control

SCADA/EMS integration

Blackout prevention, monitoring and optimization that keep the charge in its target band and orchestrate the whole system.

Let`s make this predictable

We propose a technical review of your specific connection point – capacity, functional requirements and solution design.